Sample certificate · Contactor

Schneider TeSys LC1F780: test certificate

A real certificate from a recent major service on a contactor Schneider describes as not repairable. Customer name, site and references removed; every result as recorded.

  • ContactorTeSys LC1F780 (LC1FDP780A)
  • Rating780 A AC-3 · 1600 A AC-1
  • Coil110/120 V
  • ResultAll tests passed
Schneider LC1F780 contactor with pole covers removed, contacts dressed across all three poles
Contacts dressed across all three polesCertificate

Sample. Customer name, site address and customer references have been removed. All test results are exactly as recorded.

Contactor

ManufacturerTelemecanique (Schneider Electric)
TypeLC1-F780, TeSys F range
Catalog referenceLC1FDP780A
Rating780 A AC-3 (≤440 V), 1600 A AC-1
Poles3 (3 NO)
Coil110/120 V, 40–400 Hz, sealed factory-calibrated coil module

Coil and electrical tests

TestTest VReadingResult
Coil resistance A1–A210 A9.6 ΩPass
Coil IR to earth500 V DC>1000 MΩPass
Pick-up voltage—90 VPass
Drop-out voltage—65 VPass
Low-voltage operation (85%)—Operated at 93 VPass

Main contact resistance and insulation

TestTest VL1–T1L2–T2L3–T3
Contact resistance, closed10 A DC0.073 mΩ0.071 mΩ0.057 mΩ
IR phase to earth, open500 V DC>1000 MΩ>1000 MΩ>1000 MΩ
IR phase to phase, open500 V DCL1/L2, L1/L3, L2/L3: all >1000 MΩ

Inspection and functional tests

ItemResultNotes
Enclosure / housingPassCleaned; pole covers refitted
Main power terminalsPassDressed contact assemblies fitted; terminals dressed and torque-checked
Visible arc damagePassArc-damaged pole carrier and burnt moving contacts removed, dressed and refitted
Overheating / discolorationPassNo residual signs after contact work
CorrosionPassSurface rust removed from drive shafts and mechanism rails
Coil conditionPassFactory-sealed coil module, seal intact
Energize / de-energizePass
Service operationsPass30 electrical operations
Mechanical operationPass30 mechanical operations; movement smooth, not rubbing or catching

Work completed

Major service. The contactor was stripped and inspected. One pole carrier showed severe arc damage; it was removed with its burnt moving contact assemblies, repaired and dressed, and moving contact assemblies were refitted across all three poles.

All main contacts were dressed and contact alignment and simultaneity checked. Surface rust was removed from the drive shafts and mechanism rails, and the mechanism cleaned, re-lubricated and proved free through repeated manual operation.

Defects found: no outstanding remedial work. Temperature at test: 20 °C. Completed and approved September 21, 2026.

Schneider's own guidance says TeSys F contactors can't be repaired, and the range has been obsolete since 2023. This certificate is why we disagree. LC1F contactor repair · Can an LC1F be repaired?