ABB SACE Emax E3N-A, 2000 A: test certificate

A real certificate from a recent major service, published with the customer's name, site, references and serial numbers removed. Every unit we return comes with one like this.

  • BreakerEmax E3N-A, 3-pole, fixed
  • Trip unitPR122/P LSI
  • Rating2000 A, UL listed
  • ResultAll tests passed
ABB SACE Emax E3N-A with its front cover off during the mechanism rebuild
Mechanism being rebuiltCertificate

Sample. Customer name, site address, purchase order, customer references and the breaker serial number have been removed. All test results are exactly as recorded.

Circuit breaker

ManufacturerABB SACE
TypeEmax E3N-A 20 (UL-listed low-voltage AC power circuit breaker, ANSI C37.13)
Rating2000 A, 3-pole, fixed pattern
As foundOFF, isolated, springs discharged
Trip unitSACE PR122/P, LSI, rating plug 2000 A
SettingsI1 1.0 · t1 3 s · I2 1.2 · t2 0.1 s, I²t on · I3 1.6 · ground fault off
Test methodSecondary injection, ABB Ekip SIM test kit

Protection injection test

Trip times recorded on each pole. Every result fell inside its theoretical band.

FunctionInjectedTest pointExpectedL1L2L3Result
Long time (L)3000 AI1 × 1.510.8–13.2 s11.42 s12.28 s13.17 sPass
Long time (L)6000 AI1 × 32.7–3.3 s2.821 s3.124 s3.097 sPass
Short time (S)4800 AI2 × 2, I²t1.48–2 s1.658 s1.777 s1.673 sPass
Short time (S)20000 A10 In, definite time60–140 ms72 ms79 ms85 msPass
Instantaneous (I)3680 AI3 + 15%≤ 50 ms12 ms11 ms14 msPass
Instantaneous (I)2720 AI3 − 15%No instantaneous trip4.972 s4.999 s5.012 sPass

Contact and insulation resistance

TestTest VL1L2L3
Contact resistance10 A14 µΩ10 µΩ13 µΩ
IR phase to earth500 V>1000 MΩ>1000 MΩ>1000 MΩ
IR open pole500 V>1000 MΩ>1000 MΩ>1000 MΩ
IR phase to phase500 VL1–L2, L1–L3, L2–L3: all >1000 MΩ

Accessories and mechanism

Motor operator110/120 V · Pass
Closing coil110/120 V · Pass · Replaced
Shunt trip coil110/120 V · Pass · Replaced
Undervoltage coil110/120 V · Pass · Replaced
Auxiliary contacts2 NO / 2 NC · Pass
Contact wear<20% · Pass
Arcing contact gap0.4 mm · Pass
Mechanism, springs, counter, trip indication, pushbuttonsPass

Work completed

Major service. The breaker arrived with a broken charging handle, a missing CLOSE button, and corrosion and rust contamination throughout.

The unit was stripped down and the operating mechanism fully dismantled so each component could be inspected. Parts were cleaned ultrasonically, re-lubricated and reassembled. A new charging handle and CLOSE pushbutton were fitted. The closing coil, shunt trip and undervoltage release were replaced as requested.

The protection release was injection-tested at multiple thresholds with ABB's Ekip SIM test kit, and tripped the breaker within the required times at every point. Contact resistance at 10 A and insulation resistance at 500 V were satisfactory. Over 30 mechanical service operations were performed.

Defects found: none outstanding. Parts used: ABB SACE manual charging handle (1), ABB SACE CLOSE button (1), plus the three replacement coils.

Ambient and breaker temperature at test: 23.5 °C. Completed and approved September 22, 2026.

This breaker is a first-generation Emax with a PR122 trip unit. More on Emax E1–E6 repair, the PR121/PR122 trip unit guide, or the LC1F contactor certificate.